What is temperature rise of transformer?
The temperature rise of a transformer refers to the increase in temperature of the transformer’s internal components, typically the windings and core, above the ambient temperature due to the heat generated during its operation. This temperature rise is a key factor in determining the transformer’s efficiency, longevity, and performance.
Understanding and managing temperature rise is essential for ensuring a transformer’s safe and efficient operation.
Example Calculation:
If a transformer operates at 90°C while the ambient temperature is 30°C, the temperature rise is:
Temperature rise=90℃ – 30℃=60℃
This would be within the typical range for many types of transformers, though this depends on the transformer’s design and rating.
Standards
The temperature rise test must conform to established industry standards such as:
IEC 60076-2 (for power transformers) – This standard specifies the allowable temperature rises for different transformer designs and types.
For dry-type transformers: The temperature rise limit is typically 60°C to 65°C above ambient.
For oil-immersed transformers: The temperature rise is often specified as 55°C to 65°C above ambient.
IEEE C57.91 (for transformer temperature rise and cooling) – Provides guidelines for allowable temperature rise, cooling, and the long-term impact of temperature on transformer life.
ANSI C57.12.00 – This provides general guidelines for the testing and performance characteristics of transformers.
Procedure for Transformer Temperature Rise Test
A Transformer Temperature Rise Test is conducted to measure the temperature increase in the transformer under full-load conditions. This test ensures that the transformer operates within its thermal limits and can safely dissipate the heat generated by electrical losses during normal operation. The results of the test are essential for verifying the transformer’s performance, confirming compliance with design specifications, and ensuring that the transformer will not overheat during its service life.
The Temperature Rise Test typically involves loading the transformer to its rated capacity and then monitoring the temperature over time. Here is a general outline of the procedure:
Preparation
The transformer is installed in a controlled environment where the ambient temperature is known and stable. The transformer should be energized under normal operating conditions.
The ambient temperature (the temperature of the surrounding environment) is recorded at the start of the test.
Loading the Transformer
The transformer is loaded to its rated full load (or sometimes a slightly higher load) for a period of time to simulate normal operating conditions.
The loading conditions depend on the transformer’s rating and can be done with resistive loads, variable load banks, or through simulated operational loads.
Monitoring Temperature
The temperature of the windings (primary and secondary), oil (if oil-cooled), and sometimes the core are monitored using temperature sensors or thermocouples.
Measurements are taken at intervals (e.g., every 15 minutes) to record the temperature rise of various components during the test.
The temperature rise is the difference between the measured temperature of the transformer components and the ambient temperature.
Test Duration
The transformer is loaded for a specific duration, which can range from 1 to 8 hours or more, depending on the transformer size and test specifications. The duration is long enough to allow the transformer to reach a steady-state operating temperature.
Steady-state temperature is usually achieved after 3-4 hours for smaller transformers, but larger transformers may take longer.
Recording the Results
The highest temperature reached during the test is recorded, including the temperatures of the windings, oil (in oil-cooled transformers), and ambient air.
The temperature rise is calculated as the difference between the highest measured temperature and the ambient temperature.
Cooling Down Phase
After the transformer is unloaded, the cooling rate (how quickly the transformer temperature returns to ambient levels) can also be measured, though this is less critical than the temperature rise measurement.
The cooling time provides insight into the transformer’s heat dissipation capability.
How Temperature Rise impact on transformer?
Effect on Transformer Efficiency
Losses Increase: As the temperature of a transformer increases, the electrical losses in the core (eddy currents and hysteresis) and the windings (I²R losses) also increase. This results in decreased efficiency since more energy is converted to heat rather than being transferred as electrical energy.
Reduced Performance: High temperatures can lead to increased resistance in the windings, especially for copper or aluminum windings. This means the transformer may require more input power to supply the same output, thus reducing overall efficiency.
Impact on Insulation Materials
Insulation Degradation: The insulation in a transformer (e.g., paper, oil, or resin) is designed to withstand specific temperature limits. As the temperature rises, the insulation materials age more quickly, which can lead to insulation breakdown over time.
Higher temperatures cause molecular degradation in insulating materials, reducing their dielectric strength, which increases the risk of short circuits or arcing.
Impact on Transformer Longevity
Reduced Lifespan: The operational lifetime of a transformer is closely tied to its operating temperature. For every 10°C increase in operating temperature, the rate of insulation degradation roughly doubles, significantly shortening the transformer’s life.
Effect on Load Capacity
Reduced Load Handling: Transformers are typically rated to handle a specific load based on the expected temperature rise and cooling capacity. If the transformer experiences excessive temperature rise, it might not be able to carry the rated load safely for extended periods. This could result in:
Overloading: If the transformer is forced to operate under higher-than-rated temperatures, it may enter an unsafe thermal condition where the risk of damage increases.
Reduced Performance at Full Load: With higher temperatures, the transformer may need to operate at lower loads to maintain safe operating temperatures, effectively reducing its capacity.
Effect on Transformer’s Safety
Overheating and Fire Hazards: If the temperature rise exceeds the safe limits, there is a risk of overheating. This can lead to:
Insulation failure, which can result in short circuits or electrical arcing.
Fire hazards: For oil-filled transformers, overheating can cause the oil to ignite, posing a serious fire risk.
Explosion risk: In extreme cases, failure of transformer components due to excessive temperature rise can cause catastrophic events such as oil tank rupture or explosion.
Temperature Rise Limits (Typical)
- Class A Insulation: Maximum temperature rise of 40°C to 45°C above ambient.
- Class B Insulation: Maximum temperature rise of 50°C to 55°C above ambient.
- Class F Insulation: Maximum temperature rise of 60°C to 65°C above ambient.
- Class H Insulation: Maximum temperature rise of 75°C above ambient.
Conclusion
To ensure your transformer enjoys a long service life, it’s crucial to understand its temperature ratings and thermal performance.